Commissioning — Full Explanation¶
The wizard screens carry only what you need to run each step. This page is the long version: what each step measures, how the resulting numbers are derived, and which protections are live while it runs.
For the practical walkthrough (what you press, in what order), see Automatic System Characterization. One step has a separate page: Stress Test.
Protections during characterization¶
The steps that drive the field directly or hold a fixed test current (Field curve, Current Control Autotuning, Verify Current Control, Disturbances, Voltage Control Autotuning, Keep-Alive Floor & Field Decay, and Charge Health Calibration) run with the protections that act through the voltage loop paused: the over-voltage trims, the timed over-voltage cuts, the over-current detector, and load dump. They would interfere with the measurement. The fast over-voltage hard shutdown and the hardware over-voltage shutdown are never disabled, and the hard over-current cut and the temperature cuts stay live as well.
Every other step (Prep, Fault Threshold Autotuning, and the Stress Test) runs under full normal protection. Each wizard screen states which case applies at the bottom.
A protection cut, or the field leaving Auto mode for any other reason (a shutdown ramp, Manual mode, Run Without Failed Sensors taking the field), ends the test in progress, and the wizard reports the cause. The Stress Test is the exception: it is graded on the over-voltage and over-current cuts it provokes, so those only pause it, and any other cause ends it. Every button that starts a field-driving test is disabled while the ignition input or Alternator Enable is off, and the screen says which one.
Step 1 — Prep¶
Budget about 30 minutes. Prep checks the preconditions and snapshots every setting the wizard might touch. The state-of-charge guidance and what Abort and revert all restores are under Before you start.
Other charging sources (solar, shore charger, DC-DC, wind, hydro) and large on/off loads (inverter, windlass, watermaker, electric cooking) must be off. The tests measure how your battery bank responds to the alternator alone; another active charger or a cycling load distorts the measurements, and a tune fitted to distorted data can control the field poorly later when that source is off.
Prep also reports the battery shunt and the Battery Charge Current Limit as the regulator will use them. The shunt reads OK only with Battery Shunt Present on and a shunt resistance set, and the limit reads active only when it is enabled, above 0 A, and backed by that shunt. A limit that is set without a usable shunt reads inactive, with the missing shunt condition named. This line is advisory and never blocks Start.
Step 2 — Field curve¶
An open-loop field-drive ramp across the full range maps drive → amps, finds the saturation knee (where more drive stops producing more current), and proposes the next step's wave floor (baseline current) and step size. No feedback control; raw drive only.
Step 3 — Current Control Autotuning¶
An open-loop sine sweep on field drive identifies the plant (time constant τ, gain, and delay) and proposes the current-loop gains and filter time constants. The gains are stored in 12 V-equivalent terms (divided by Field Winding Voltage over system voltage), the scale the PID gain boxes use, so the loop applies exactly the gain the sweep measured.
This characterizes the alternator's field → current behavior, so it runs on alternator current, the same signal the inner loop regulates in every mode. Wave floor and step size carry over from the Field curve step's proposal (the Plant Delay tab).
The sweep frequency range is fixed at 0.5–20 Hz, widening to 0.3–30 Hz on an automatic retry.
Engine speed is never gated. Run near the Field curve's speed, because the carried-over sizing and the fitted gains both track speed. The wizard only flags a result more than ±500 RPM off, or one where speed varied more than 500 RPM mid-sweep.
Step 4 — Verify Current Control¶
A closed-loop check: it drives the target current as a sine from slow to fast and measures overshoot (peak gain must stay at or below 1.15, or the loop rings toward over-voltage) and speed (bandwidth), on alternator current.
It sweeps past the speed the loop can follow on purpose. The response going small and irregular at the highest frequencies is how the bandwidth is found, not a bad reading. Check the raw sweep on the Current Control plot before accepting.
A peak gain above 1.15 fails the check, and the screen offers Soften 20% & re-verify. It lowers the current-loop proportional and integral gains by 20%, saves them, and runs the check again.
Step 5 — Disturbances¶
This step records the low-frequency disturbance at each engine speed into a map. You can stop as soon as the worst-ripple speed is identified and no unswept gap could hide a bigger peak; there is no need to cover every speed.
During the sweep the wizard holds the alternator at one fixed test current, because ripple scales with current. The starting figure is 25% of the largest limit in your RPM table up to 2000 RPM. The regulator holds every wizard test current to the RPM table's limit at the engine speed of the moment, and a speed held below the target records nothing, so the wizard lowers the current to the smallest limit the table allows anywhere in the sweep band when that is less. The band runs from about 50 RPM below your measured idle up to 2000 RPM. The screen shows the current and the band and asks you to confirm before the field is armed. A table that allows 1 A or less anywhere in the band stops the sweep before it starts.
The sweep captures the measured filtered ripple (the same signal the over-current detectors trip on, averaged over their Averaging Time Constant) per RPM bin, for the alternator current and, when a battery shunt is fitted, the battery current. A value only commits when two readings at that speed agree, so a throttle transient cannot corrupt the table.
The optional current check then commands three current levels at the worst-ripple RPM (30, 60, and 90% of the RPM table's limit at that speed) and fits ripple = a0 + a1·I on alternator current. The same windows also capture how fast that ripple moves the smoothed battery voltage (V/s, through the voltage-loop damper's filter) and fit it the same way.
If a protection cuts the field, or the field leaves Auto mode, while the sweep or the current check holds its current, the regulator ends the hold and the wizard stops the step with the cause. After an over-voltage cut it reports that the battery could not take that current at that engine speed: run the step again at a lower state of charge. Whenever the table's limit at the present engine speed is below the commanded test current, the regulator holds the current at the limit and says so once on the console.
This produces the measured projections only; it never sets a threshold. Review them against your settings in the next step, on the Protections ripple plot, and on the Tuning deadband plot.
Step 6 — Fault Threshold Autotuning¶
This step sets the over-current trip line from the ripple measured in Step 5.
The trip line is Slope · current + CV base, floored and capped. Slope is set to
the measured ripple slope, and CV base to the fit's ripple at zero current plus
the Safety Margin, so the line runs parallel to the ripple, that margin above it. The
current-limited (CC) line runs the same slope, the CC offset above the
voltage-holding (CV) line. Any current where the ripple would cross the line is
shaded red.
These are the exact Group 3 settings on Setup ▸ Alternator ▸ Protections, and editing them here writes them live.
Why lead-acid and AGM get a much larger margin¶
On a lead-acid or AGM bank the recommended margin is large, 30 A, because a brief current spike does these batteries no harm. Their wear accumulates over minutes to years, not milliseconds, and there is no lithium-style BMS cutoff. Setting the trip high lets a momentary over-current from a brief engine-speed change ride through, so the current loop brings it back down instead of cutting the field and dropping the charge for a fraction of a second. The battery-voltage protections still act fast on an actual over-voltage. The ceiling is raised to match, so the larger margin is not clipped back down.
On lithium, 5 A suits most installations.
Voltage-Rise Tolerance (the D-term deadband)¶
The second section sets the voltage-loop damper's deadband line the same way: slope = the measured rise-rate slope, base = the measured intercept plus a separate Safety Margin (V/s), clamped by its floor and ceiling. Those are the Voltage-Rise Tolerance settings on Setup ▸ Alternator ▸ Tuning ▸ Voltage. If Step 5 was skipped there is no fit, and both must be set by hand.
The damper (the D term) ignores voltage movement slower than its deadband, so ordinary belt and diode ripple cannot make it change the field drive. Commissioning has already measured this installation's ripple rise rate (the Step 5 current check) and set that threshold automatically, as a line that climbs with output current, since ripple moves the voltage faster at higher current.
The Safety Margin on that screen is not the threshold itself; it is the safety factor added to it: how far above the measured ripple the whole line is set. Larger means fewer nuisance engagements but a later reaction to a genuine fast rise; the over-voltage protections still act fast on it.
Each fit is valid only for the conditions it was measured under. Changing the over-current Averaging Time Constant discards the ripple fit, changing the D-term voltage filter discards the voltage-rise fit, and changing the ripple Capture Window or the engine-speed calibration discards both. The Step 5 current check then has to run again to replace them. The Safety Margin Set buttons on Setup ▸ Alternator ▸ Protections and Setup ▸ Alternator ▸ Tuning ▸ Voltage read the stored fit from the regulator at every press. If that read fails, or no fit is stored, nothing is changed and the screen says so.
Step 7 — Voltage Control Autotuning¶
This step measures how stiff the battery is (how many millivolts it moves per amp) at the voltage loop's reaction timescale, about 0.6 s, so the loop's stability margin comes out the same on any battery. A multi-second reading is mostly slow diffusion "soak", which differs widely between lithium, AGM, and flooded banks.
The sequence: settle at a baseline current, size a safe test step (automatically reduced if the bank nears its over-voltage ceiling), practice-hold at the step through the current loop to measure its field level, come back down to the baseline to learn that one, then fire four abrupt field pulses, reading the settled voltage change 550–650 ms after each edge against the settled current change. The result is the median over the eight edges, so a disturbed edge is discarded rather than biasing the answer; at least three must remain.
If the bus comes within 0.10 V of the Alternator Hard Shutdown Voltage at any point in the hold, the return to baseline, or the pulses (a 12 V figure, scaled with the system voltage), the run stops at once. The wizard reports the test step, the bus voltage, and the margin. Draw the bank down with loads or turn off other charge sources, then run it again.
The two field levels are learned consecutively, one settle apart, on purpose. The pulses replay them as fixed drive levels, so both have to describe the same alternator at the same moment. Learning them minutes apart lets engine speed move between them, and the replayed pair then steps the output barely at all.
Engine speed does not have to be perfectly steady. Adding the test step loads the engine and pulls it down a little, and that sag is part of what gets learned, so the pulses reproduce it rather than counteract it. Speed drift is measured and reported with the result. It is compared at matching points, so the sag the test causes is not counted as drift, and it never blocks a run. What does stop a run is the alternator having too little current range: if the two learned levels come out less than 2 A apart, there is no step to measure and the wizard says so instead of spending 18 seconds pulsing.
Measurement is taken at the battery shunt, or at the alternator sensor when no shunt is fitted (with loads held steady the two are equal). On anything but lithium the run does not start if the step would drive the bank into gassing, which reads the resistance low. Draw it down with some loads first.
Gains follow as Kp = α ÷ stiffness, Ki = ρ × Kp, Kd = Td × Kp, computed in 12 V-equivalent terms (the stiffness is scaled by 12 ÷ system voltage first) and each clamped to a safe range. The voltage-loop gain source switches to Measured on Apply.
Keep all other battery loads constant during the test.
Step 8 — Keep-Alive Floor & Field Decay¶
Two measurements per held speed.
The onset point. Field ramps briefly until output current just begins. Onset follows a 1/RPM law, so three points fit the whole Keep-Alive column, set a margin below. Tachometer Keep-Alive Automatic Learning (on by default) then maintains them over alternator life, but only ever lowers a floor and never raises one back up. Above your highest captured RPM the floor is forced to zero, so the field can always shut fully off at speed.
The field drain. The current loop ramps to the commissioned test level, the drive is frozen for 5 s to get a settled baseline, and the field then steps to the exact floor a real over-voltage cut drives to (the flat Min Field %) while the decay is recorded on the 20 kHz current channel, calibrated against the precision sensor during the same run. If that channel is unavailable the precision sensor's data is used for the fit instead, and the result is marked coarse.
The stored number per speed is the measured time from field-off command until output has decayed to within 10% of the residual floor (90% of the way down from its pre-cut level to that floor), read directly off the trace, with no model. The fitted time constant (τ = L/R) is reported as a cross-check.
Drain time varies with engine speed, so a straight line is fitted through the three measured speeds, shifted up to sit at or above every measured point. The over-voltage response reads that line at the engine speed latched when the episode began, held constant beyond the tested range and never extrapolated.
Both here and during the test, speed is taken before the cut, because the cut makes the tach signal unreliable for a few seconds; the tach gates are suspended during each run for the same reason. Field at the cut floor cannot over-volt, so the drain runs are inherently safe.
Step 9 — Stress Test¶
The graded test, with a separate page: Stress Test. It charges at idle (at least 10 seconds) until the voltage settles, holds the bus at a constant-voltage target a set headroom below that level (Target Headroom Below Idle, on the Stress Test tuning tab), then has you snap the throttle to deliberately fire the over-voltage protection, and grades the recovery: clamp count, any hard current cut, recovery time, and post-recovery stability. The settle rules, arming logic, and grading thresholds are all on the Stress Test page. It writes no settings, so skipping it never blocks the COMMISSIONED badge; it is a reference check you can run any time.
Settling onto the lower target is given up to 90 seconds, and a voltage holding steady near the target (even slightly short of it) when that wait runs out still arms the test, graded marginal (the stability limit is adjustable on the same tab). The recovery measurement gets a full window that starts at the trip, so taking your time before snapping can never inflate the recovery time and a late snap can never shorten it. A snap under about 300 RPM above the armed speed does not register as a snap at all, and the run ends without a grade. There is no Finish button: the test ends itself once the voltage has settled back, and Cancel only aborts the run ungraded.
Step 10 — Charge Health Calibration¶
With the field held at a fixed level, alternator output follows where engine speed is going rather than where it is: the rotor holds its flux for a few tenths of a second, so a climb through a given speed reads higher than a descent past the same speed. This step measures the delay that makes the two agree and stores it as the Output lead. The charging-system health tracker uses that number to pair each output reading with the engine speed that produced it, so the readings it takes while the boat is under way are graded against the right speed.
The test goes no higher than half your maximum working RPM. That number comes from Step 8, whose first hold is at the highest speed you normally run, and it is under Advanced on this screen if you want to change it. The screen asks for it only when none is on file, or when the one on file leaves the test too little range above today's idle (the top has to be at least 400 RPM above idle), and it says so before any driving. The test current defaults to half the charge-rate limit at the test top, taken from the Low column on banks under 201 Ah and the High column at or above it; the stepper under Advanced adjusts that share between 20 and 80 percent in steps of 10, and you lower it only if a run stops early and you have to repeat the exercise.
The run is four cycles, continuous from the first to the last: nothing to press between them, and nothing telling you to stop or reverse direction. The first cycle opens with ten seconds at idle, and every cycle climbs from idle to the test top, holds there, and descends back. The current loop tuned in steps 3 and 4 brings output up to the test current during the first climb, and the field drive is frozen through the first hold, which lasts about eight seconds so the loop can settle. Later holds run about three seconds.
Sizing the field at the top of the range is deliberate. That is the fastest the alternator turns during the run, so it is where output and bus voltage are highest, and every later moment produces less than the sizing step already demonstrated.
Pace each cycle at roughly five seconds per 1000 RPM. The screen draws the whole cycle before it begins: a shaded band of acceptable engine speed against time, a dashed line through the middle of it, and a small boat marking where you are right now. The boat is teal inside the band and amber outside, and it leaves a trail behind it so you can see how the cycle went. Adjust the throttle to keep engine speed inside the band.
The band is two allowances added together. You may run up to two seconds ahead of or behind the schedule, and in addition you have 250 RPM or 15% of the speed you are at, whichever is larger. The schedule is flat while you hold at the top, so the time allowance adds nothing there; on the climbs and descents it widens the band by about 400 RPM. Samples taken slower than 40 RPM per second carry no direction information and are discarded.
Both directions are required, because a single direction cannot separate a time shift from the shape of the speed curve. Each of the three cycles after the first produces one independent answer; the first produces none, because its climb happens before the field is frozen. The closest two of the three are averaged and rounded to a tenth of a second, the resolution the health tracker's delay line holds, and that is the number stored. The third is discarded, and the screen shows all three with the discarded one marked. Answers that disagree by more than 30% are rejected and the run has to be repeated. A load switching mid-cycle, or a throttle movement that paused part way, causes that. A run that yields only one answer stores nothing and has to be repeated too, since there is nothing to check that answer against.
The fourth cycle reaches idle and the run ends itself. It ends early if output reaches 95% of the High charge-rate limit for the speed you are at, or if the bus comes within 0.02 V of the charge target (on a 12 V system; the margin scales with the system voltage); the wizard then says which ceiling it hit and offers the run again with the test current already reduced by one step. A protection cut also ends the run. A start pressed while the engine is not running expires after 30 seconds. The screen reports the minimum, average, and maximum throttle pace you delivered, in RPM per second, for reference.
This step needs a battery that will still accept current, which is not true every day, so it is optional: skipping it never blocks the COMMISSIONED badge, and you can run it any time the bank will take a charge. Like the other held-field steps, it runs with the voltage-loop protections paused and the absolute cuts live.
Cross-references¶
- Automatic System Characterization: the walkthrough.
- Stress Test: the graded test in detail.
- Safeties & Protections: how the protection layers work together.