Skip to content

Protection Timing

The protection ladder says what fires and in what order. This page is the reasoning to read before moving any of the over-voltage thresholds or times to act.


The problem being solved

Every field cut is a mechanical event. An alternator under load resists the crank with real torque; cutting the field removes that torque in tens of milliseconds, and the engine reacts with a lurch, a belt snap, or a rev flare at idle. A regulator that cuts instantly on every brief excursion is felt constantly, and most of those cuts are unnecessary: the excursion would have resolved under the proportional current shed without a cut.

The regulator can cut in milliseconds, so the design question is how fast it needs to cut. The answer is set by the other protection system on the bus: the battery management system (BMS).

What a lithium BMS does

The controlling hazard on a lithium bank is the BMS opening its charge path under load. An alternator feeding a bank that suddenly disconnects is a load dump: the field is energized, the load vanishes, and the bus voltage rises until something absorbs the energy. The regulator must therefore always act first; the BMS should never be what ends a charge event.

A survey of the charge-disconnect criteria published for marine lithium batteries supports two conclusions:

  • No known BMS opens its charge path on any event shorter than 0.5 seconds. Where qualification delays are published at all they run 1 to 4 seconds; the rest publish threshold-only criteria whose practical response is no faster.
  • The voltage comparators are per-cell, referenced to the highest cell. Published charge-disconnect voltages start just over 3.6 V per cell (14.5 V on a 4-cell 12 V bank) and run up toward 3.9 V per cell. Current-side disconnects, where published at all, are set near 1C with hold times from half a second to minutes.

First, a transient shorter than half a second, at any amplitude up to the software hard cut, is invisible to every BMS: the BMS will not disconnect, so there is no reason to cut the field over it. Second, any sustained violation must be fully resolved, field de-energized, before that half-second is up.

The 0.4-second rule

De-energizing the field is not instant: the coil's stored energy takes roughly 100 ms to bleed after the cut (the actual figure is measured for each installation during commissioning, in the field-decay characterization). Budgeting that out of the 0.5 s floor leaves 0.4 seconds as the working rule:

Any excursion that persists is cut within 0.4 s of crossing the lowest trip line. Anything shorter is ridden through while the proportional shed works on it.

That single rule generates the timed tiers, and the margin arithmetic below generates the thresholds.

The ladder, and why each rung is where it is

12 V lithium defaults shown; every voltage scales with the system voltage class (× class/12). The AGM and flooded rungs, and the 48 V column for all three chemistries, are tabulated under Recommend Initial Charging Settings.

Rung Threshold Time to act Why it is there
Proportional shed (Group 2) target + 0.10 V continuous Sheds current in proportion to the excess. Resolves most excursions with no cut and nothing felt at the engine.
Timed cut, LOW tier target + 0.10 V 0.4 s The 0.4-second rule itself. It uses the shed threshold, so the shed always has the whole 0.4 s dwell to end the excursion before a cut.
Timed cut, MID tier target + 0.20 V 0.15 s A larger excess gets a shorter delay — an inverse-time characteristic, like a breaker curve.
Software hard cut 14.2 V absolute instant The amplitude bound. Logged, lockout-managed, recoverable — the preferred hard trip.
Hardware shutdown (INA228 alert pin) 14.3 V absolute instant, electrical Fires with no firmware involved. Exists for exactly one case: firmware that is hung, crashed, or mid-update.
BMS charge disconnect ~14.5 V and up ≥ 0.5 s Never reached, by design.

The two absolute rungs are deliberately ordered software-first. The software cut produces a named reason, a counter, an adaptive lockout, and a managed recovery; the hardware pin cuts the field without firmware, and the firmware adds a named reason and a count when it finds the over-voltage still present at its next check (within 5 s). In a healthy system every hard trip should be a software trip, and a nonzero hardware-cut count is itself diagnostic: it means software failed to act.

The timed tiers measure their dwell against the same filtered voltage the shed uses, and the clock is strict: one tick back under the line resets it. A ripple crest that briefly crosses the line accumulates nothing; only a bus that stays above the line for the full dwell trips the cut. The clock also runs only while the alternator is producing more than its no-output current (NoOutputAmps, 2 A by default), or while its current reading cannot be trusted. A bus held above target by solar or shore power, with the alternator near zero, therefore does not trip a tier.

Placing the two absolute rungs for a specific battery

The defaults are placed against the lowest surveyed BMS floor, so they are safe for an unknown battery. For a known battery they can be set precisely:

  1. Find the BMS charge-disconnect voltage per cell in the battery documentation (it may be called high-voltage disconnect, overvoltage protection, or charge cutoff). Multiply by the cell count for the pack-referred value.
  2. Set the Hardware Shutdown Voltage 0.2 V (× class/12) below it. The margin is 0.2 rather than 0.1 because the BMS trips on its highest cell while the regulator measures pack voltage. On a 12 V bank, 0.1 V of pack margin is only 25 mV per cell, which routine cell imbalance can consume.
  3. The Alternator Hard Shutdown Voltage (software) is set 0.1 V (× class/12) below the hardware value; the firmware enforces the order on every write and at boot.

For flooded and AGM lead-acid there is no BMS, and every lead-acid damage mechanism integrates over minutes to years, so a brief bounded excursion above bulk does the battery no measurable harm. Their hardware ceiling (16 V on a 12 V bank) instead protects the connected DC loads, whose published continuous ratings have a maximum near that level, with the software cut 0.1 V under it. That ceiling is an equipment rating and not a per-cell one, so it stops scaling: on a 48 V bank it holds at 60 V rather than following the class to 64 V, and the three target-relative rungs beneath it are compressed by one common factor to fit underneath.

Why the hardware rung cannot be the timed one

Making the independent hardware comparator the 0.4-second layer is not possible. The INA228's alert compares against its internally averaged reading, and the chip has exactly one averaging depth shared by every input: slowing the voltage comparison to hundreds of milliseconds would slow the battery-current measurement to the same cadence, starving the load-dump detector and the charging loop of the current samples, read about every 6 ms, that they run on. The averaging is therefore left shallow (about 4.5 ms while the field is live), the pin stays instant, and the timed behavior is implemented in software where each tier has a separate timer.

Timing on the current side

  • Hard overcurrent (the electronic fuse) debounces for 40 ms: above sensor noise, and far inside the budget of any real fault.
  • Load-dump detection cannot wait: when a large load drops off the bus while charging, the current it drew flows into the battery within milliseconds. A BMS opening the charge path is the opposite current signature, battery current falling toward zero, and the voltage rungs above catch it. Each tier counts consecutive battery-current readings, taken about every 6 ms (up to about 18 ms worst case). The output is cut at the next control update, which comes about every 13 ms (up to about 30 ms worst case). At the shipped counts the one-sample tier acts in about 6 to 19 ms (up to about 48 ms worst case) and the two-sample tier in about 12 to 25 ms (up to about 66 ms). Each tier's time to act is shown directly under its setting, so the trade is visible rather than implied.
  • The sustained current-excess supervisors already work on a time-averaged signal (75 ms averaging); their response time is set by the threshold-versus-ripple margin, not by a debounce, and needs no adjustment under this rule.

What to expect in practice

With the ladder timed this way, brief excursions (an RPM blip cresting over target, a moderate load step, a wave-induced surge) end under the proportional shed with no cut and no lurch. Field cuts still happen, but each one now means something specific: a bus that stayed above a trip line for its full dwell, an absolute threshold crossed, or a genuine load dump. The lifetime overvoltage counters on the Safeties and Protections page count how often each rung acted; a healthy installation accumulates shed engagements and little else.